Modular 400kVA – 800kVA PF 1.0

Download Brochure

Features

  • Dual DSP digital control technology
  • Flexible modularity and easy scalability with all hot-swappable module design
  • High efficiency at low load rate: 97% at 40% rated load and 96% at 20% rated load
  • High power density of 100 KVA/3U power module
  • Wide input voltage range, high grid adaptability, strong load adaptability and strong overload capability
  • Small footprint (600 KVA system only 0.8 m2 footprint)
  • Inbuilt integrated PDU system, easy installation and saving investment
  • Input power factor > 0.99, THDI <3%, environment friendly and high-efficiency and energy-saving
  • Soft-start technology improves generator matching up to 1:1.1
  • Support two modes of frequency conversion: 50 Hz input/60 Hz output and 60 Hz input/50 Hz output
  • Intelligent hibernation design enables UPS to operate efficiently at low load rate to prolong service life and improve the system efficiency
  • Advanced parallel expansion technology, support 4 units in parallel
  • Flexible charger parameter and battery configuration setting, numbers of battery 30-50 pcs selectable
  • Intelligent battery management (Intelligent charge/discharge management and float charging voltage temperature compensation), extending battery lifespan
  • Support battery cold start and utility self boot
  • Self-aging function, easy debugging and test on site
  • Fault-tolerant design for fan system: 20% load can be driven when 2 fans fail and 50% load when 1 fan fails
  • Front accessible maintenance, top/bottom cable entry compatible
  • Complete hardware and software protection function, robust self-diagnostic function, and abundant event log for check
  • 7 inches LCD touch screen, friendly human-machine interface
  • Monitoring unit with built-in SNMP, supports RS485 and dry contacts

Specifications

MODEL 400kVA 500kVA 600kVA 800kVA 1000kVA 1200kVA
Related Capacity 400KVA 400KW 500KVA 500KW 600KVA 600KW 800KVA 800KW 1000KVA 1000KW 1200KVA 1200KW
Numbers of Power Modules 4 5 6 8 10 12
Related Capacity of Power Module 100KVA / 100KW
INPUT
Input wiring3 Ph + N + PE
Rated voltage380 / 400 / 415 Vac
Voltage range138 ~ 305 Vac (linear derating at <40%, 100% load), 305 ~ 485 Vac (no derating)
Input Frequency range40 ~ 70 Hz
Power factor≥ 0.99
Current Distortion ≤ 3%
BATTERIES
Battery voltage480 Vdc (360 ~ 600 Vdc settable)
Number of battery40 pcs 12 V batteries (30 – 50 pcs settable)
OUTPUT
Output wiring3 Ph + N + PE
Rated voltage380 / 400 / 415 Vac ± 1
Frequency Synchronized with utility in mains power mode; 50 Hz / 60 Hz ± 0.1% in battery mode
Power factor1.0
Voltage distortion ≤ 1% (linear load); ≤ 4% (non-linear load)
Crest factor3:1
Inverter Overload capacity 105% ≤ load ≤ 110% for 60 min,
110% ≤ load ≤ 125% for 10 min,
125% ≤ load ≤ 150% for 1 min,
load > 150% for 2 s
Bypass Overload CapacityLoad ≤125% for long term ; 200% load for 100 ms
SYSTEM
Efficiency97%
Max. number of parallel connections4 units
Transfer time0 ms
ProtectionsShort-circuit, overload, over-temperature, battery low voltage, overvoltage, overcharge, fan failure protection
Communications RS 485, dry Contacts, SNMP
Display7 inches LCD touch screen
OTHERS
Operating temperature0°C ~ 55°C
Storage temperature-25°C ~ +55°C
Humidity0 ~ 95%
Altitude≤ 1000 m, above 1000 m, derating 1% for each additional 100 m
Protection levelIP 20
Cabinet dimensions (W × D × H)(mm)800 × 1000 × 2000 2000 × 1000 × 2000
Cabinet Packing Dimensions (W × D × H)(mm)900 × 1100 × 2190 2100 × 1100 × 2190
Power Module dimensions (W × D × H)440 × 750 × 130
Power Module Package (W × D × H)604 × 1004 × 268
6 Power Module Package (W × D × H)1250 × 1030 × 940
Cabinet net weight (kg)412 kg920 kg
Cabinet packing weight (kg)450 kg1010 kg
Power module weight (kg)50 kg
Power module packing weight (kg)55 kg